AVK HIGH PRESSURE, 200 PSI, WET BARREL HYDRANT

UL/FM approved. 2 x 2½" + 1 x 4/4½" outlets

AVK UK Gas and Water Sales

AVK UK

Gas & Water Sales

Wet barrel hydrant with 2x2½" + 1x4/4½" outlets to AWWA C 503 for fire protection application

AVK wet barrel hydrant is designed to be a trouble free, easy to maintain hydrant. The hydrant is rated for a working pressure of 200 psi, is UL listed and FM approved, and meets or exceeds the requirements of the AWWA C503 standard for wet barrel fire hydrants (where applicable). AVK series 24 hydrant and hydrant tools are designed so that one person can perform all routine repairs and maintenance outlined in the manual.

fire
fire
Variant 24/90-001
Connection: Flanged
Material: Ductile Iron
PN: AWWA C503
Closing direction: Clockwise to Close

Features

  • Operating nuts: 1 1/2" pentagon
  • Outlets: 2 x 2 1/2" NST hose outlets, 1 x 4" or 4½" NST pumper outlet. Optionally pumper outlet as 1 x 5" Storz, and additional 4" flanged outlet cl. 150 for Monitor.
  • Inlet: 6" AWWA flange inlet (standard)
  • UL listed and FM approved
  • Meets or exceeds AWWA C503 (latest)
  • High pressure rating (200 psi)
  • Ductile iron nozzle section
  • Each stem sealed with two O-rings
  • Replaceable cast iron dummy nuts for extra stem protection
  • Removable nozzles secured with external stainless steel allen screws
  • Fusion bonded polyester coating red RAL 3000

Downloads

Price list
Installation, Operation & Maintenance
Datasheet
Certificate(s)

Components

1. Body Ductile iron
2. Stem nut Bronze
3. Lock screw Stainless steel 316
4. O-ring NBR rubber
5. Stem Cap Cast iron
6. Dummy nut screw Stainless steel 316
7. Stem seal O-ring NBR rubber
8. O-ring NBR rubber
9. Chain Stainless steel 316
10. O-ring NBR rubber
11. Nozzle Bronze
12. Cap gasket NBR rubber
13. Cap Cast iron
14. Lock screw Stainless steel 316
15. Disc
16. Thrust collar
17. Thrust nut
18. O-ring NBR rubber
19. Stem Alu-bronze C63020
20. Screw Stainless steel

Test/Approvals

  • Hydraulic test according to AWWA C503, Shell test 400 PSI (2 x Working pressure).
  • FM Approved. UL and ULC listed.

Standards

  • Designed according to AWWA C503
0 Files In the package